NORDEN 10kVA Online Transformer less Rack Mount UPS

 

Specifications:

Features Specifications
Model CN7010MP-RM
Capacity 10000 VA / 9000 Watts
Normal Voltage 220/230/240Vac [L+N+PE]
Operating Voltage Range 110-286Vac
Operating Frequency Range 40-70Hz (50/60Hz Auto-Sensing)
Power Factor 0.99
Bypass Voltage Range Max: 220V: +25% (optional +10%, +15%, +20%)
230V: +20% (optional +10%, +15%)
240V: +15% (optional +10%)
Min: -45% (optional -20%, -30%)
Bypass Frequency Range ±10%
ECO Range Same as the bypass
Generator Input Support
Output Voltage 220/230/240Vac
Output Power Factor 0.9
Voltage Regulation ±1%
Frequency (Line mode) 50/60Hz ±0.1Hz
Frequency (Batt mode) 50/60Hz ±0.1Hz
Current Crest Ratio 3:1
Harmonic Distortion (THDv) ≤3% with linear load, ≤5% with non-linear load
Efficiency >94%
Battery Voltage 192/216/240Vdc (16/18/20pcs)
Backup Time Depends on the capacity of external batteries
Typical Recharging Time 6-8 hours (to 90% of full capacity)
Charging Current Maximum current 10A; charging current can be set according to battery capacity installed
Transfer Time Mains to battery: 0ms; Inverter to bypass: 0ms

Protection:

Features Specifications
Line Mode Overload Loads ≤110%: 60min; ≤125%: 10min; ≤150%: 1min; >150%: turn to bypass mode
Bypass Mode Overload 63A (Input breaker)
Short Circuit Hold whole system
Overheat Line mode: Turn to bypass; Backup mode: shut down UPS immediately
Battery Low Alarm and switch off
Self-Diagnostics Upon power on and software control
Battery Management Advanced battery management

Indicators and Alarms:

Features Specifications
Audible & Visual Alarms Line failure, Battery under voltage, Overload, System fault
LED & LCD Display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault
LCD Display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time

Communication Interface:

Features Specifications
Communication Interface RS232, USB, SNMP card (optional), Relay card (optional)

Physical and Environmental:

Features Specifications
Dimension (W x D x H) 440 x 625 x 86.5 mm (2U)
Weight 18 kg
Operating Temperature 0-40℃
Storage Temperature -25-55℃
Humidity Range 20-95% (Non-condensing)
Altitude <1500m
Noise Level <58dB at 1 Meter
IP Rating IP 20

Standards:

Features Specifications
Safety CE: IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, IEC61000-2-2

External Battery Pack:

Features Specifications
Model CNBC10120CR
Battery Type VRLA (Valve Regulated Lead Acid Battery – SMF)
Typical Battery Recharging Time 6-8 hours (to 90% of full capacity)
Typical Battery Life 3-5 years, depending on discharging cycle and ambient temperature
System Voltage 240Vdc
Battery Quantity 20 PCS
Capacity 9Ah/12V
Dimension (W x D x H) 440 x 680 x 131 mm (3U)
Net Weight 58/63 kg
Operating Environment 0℃-40℃
Relative Humidity 0-95% (Non-condensing)
Noise Level <40dB at 1 Meter

 