Product Details

Download

NORDEN 2kVA Online Transformer less Rack Mount UPS

 

Specifications:

Characteristic Value
Model CN7002MPI-RM/CN7002MPE-RM
Capacity 2000 VA / 1800 Watts
Phase Single phase with ground
Normal Voltage 208/220/230/240Vac
Input Voltage Range 110~300Vac (176-264Vac @ 100% load)
Frequency Range 40-70Hz (50/60Hz Auto Sensing)
Power Factor 0.9
Output Voltage 208/220/230/240Vac
Voltage Regulation ±1%
Frequency Range (Synchronized range) 46-54Hz/56-64Hz
Frequency Range (Batt mode) 50Hz/60Hz ±0.1Hz
Current Crest Ratio 3:1
Harmonic Distortion (THDv) ≤3% THD (Linear load), ≤5% THD (Non-linear load)
Efficiency 91% (AC mode), 87% (Battery mode)
Transfer Time AC to DC: Zero, Inverter to bypass: 4ms (Typical)
Waveform Pure sinewave

Battery:

Characteristic Value
Battery Type 9AH/12V
Number of Batteries 6
Typical Recharging Time 4 hours recover to 90% capacity
Charging Current (max.) 1.0A
Charging Voltage 82.2Vdc ±1%
External Battery Number 6
External Charging Voltage 82.2Vdc ±1%
External Charging Current 12A

Indicators and Alarms:

Characteristic Value
LCD Indicators Load level, Battery level, AC mode, Battery mode, Bypass mode, Fault indicators
Battery Mode Alarm Beeping every 4 seconds
Battery Low Alarm Beeping every second
Overload Alarm Beeping twice every second
Fault Alarm Continuously beeping

Physical and Environmental:

Characteristic Value
Dimension (W x D x H) 440 x 600 x 86.5 mm (2U)
Net Weight 19.5 kg (Standard model), 25 kg (Long run model)
Operating Environment 0-95% RH @ 0-40℃ (Non-condensing)
Noise Level <50dB @ 1 Meter
IP Rating IP 20

Management and Standards:

Characteristic Value
Communication Port Smart RS232/USB
Optional SNMP Power management from SNMP manager and web browser
Safety CE; IEC/EN62040-1, IEC/EN62477-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, IEC61000-2-2

External Battery Pack:

Characteristic Value
Battery Type VRLA (Valve Regulated Lead Acid Battery – SMF)
Typical Battery Recharging Time 6-8 hours (to 90% of full capacity)
Typical Battery Life 3-5 years, depending on discharging cycle and ambient temperature
System Voltage 72Vdc
Battery Quantity 12
Capacity 9Ah/12V (7Ah/12V optional)
Dimension (W x D x H) 440 x 710 x 86.5 mm (2U)
Net Weight 44.0 kg
Operating Environment 0℃~40℃
Relative Humidity 0-95% (Non-condensing)
Noise Level <40dB at 1 Meter

 

Quick Enquiry